MIM-B16UN is the same as MIM-B16N. The only difference is MIM-B16UN has an updated power cord for North America. Pulse Input Module (PIM) used in conjunction with DMS2 and DMS2.5 gateways for energy monitoring. MIM-B16 is compatible with DMS2 gateways (MIM-D00A, MIM-D00AN, MIM-B17, MIM-B17N, MIM-B18, MIM-B18N) and DMS2.5 gateways (MIM-D01AUN, MIM-B17BN, MIM-B17BUN, MIM-B18BN, MIM-B18BUN) with firmware version 2.5.x or older. MIM-B16N and MIM-B16UN is compatible with DMS2 gateways (MIM-D00A, MIM-D00AN, MIM-B17, MIM-B17N, MIM-B18, MIM-B18N, ) and DMS2.5 gateways (MIM-D01AUN, MIM-B17BN, MIM-B17BUN, MIM-B18BN, MIM-B18BUN) with firmware version 2.5.X or later. MIM-B16N and MIM-B16UN can monitor electricity, water, and gas meters that provide a pulse output.
Samsung Electricity Meter Interface Module, DVM S Series, 110-240 V, 3 A, 50/60 Hz, 12 V, 10 in H x 9-3/8 in W x 2-1/2 in D
Amperage Rating3 A
Dimensions10 in H x 9-3/8 in W x 2-1/2 in D
Frequency Rating50/60 Hz
Power Supply12 V
SeriesDVM S Series
Voltage Rating110-240 V
Pulse input module (PIM) for Samsung DVM S Series heat pump and heat recovery systems
Can also monitor pulse signals from water, gas, and electricity meters to monitor consumption from other devices via DMS2, DMS 2.5, or SNET3 interfaces.
Maximum 8 X pulse-type watt-hour meters (with appropriate CT's) per MIM-B16UN
Communicates to the following Samsung controllers/gateways: MIM-D00AN, MIMD01AUN, MIM-B17N, MIM-B17BUN (firmware version 2.6.X and later), MIM-B18N (firmware version 2.6.X and later), MIM-B18BUN (firmware version 2.6.X and later) to monitor/record energy consumption
Maximum 8 X MIM-B16UN connection to a single Samsung gateway/controller
Connection of ON/Off Controller (MCM-A202DUN), DVM outdoor unit(s)(R1/R2, C1/C2), SNET Mini (MST-S3W) cannot connect to the same channel on a Samsung controller/gateway as MIM-B16UN
Energy consumptions data can be reviewed via the following Samsung controllers/gateways: DMS 2.0 (MIM-D00AN), DMS 2.5 (MIM-D01AUN), BACnet gateway (MIM-B17N / MIM-B17BUN), LonWorks Gateway (MIM-B18N / MIM-B18BUN), SNET 3 Software (MST-P3P)
DC 12V, 3A power provided by AC/DC adapter (input 110-240VAC 50/60Hz, provided with MIM-B16UN)
16 AWG X 2 shielded cable between Samsung equipment and controls is necessary for proper operation
Connection cable between MIM-B16UN and watt-hour meter: unshielded, 16 AWG X 2, maximum 328'
One watt-hour meter (with appropriate CT's) per input channel on MIM-B16UN
One watt-hour meter per outdoor unit (single unit or modular system)
When monitoring power of indoor equipment, only units (indoor, MCU, EEV kit) on a single system can be monitored per watt-hour meter (multiple refrigerant systems on one watt-hour meter is not allowed)