The duct S allows for flexible installation with its slim design, high external static pressure and advanced fan tuning functions.
Samsung Duct S High Static Pressure Duct Air Conditioner, Series: FJM Series, 208/230 V, 2.1 A, 153 W, 60 Hz, 1 ph, 3 Number of Fan Speeds, 15000 Btu/hr, 307 cfm, 374 cfm, 441 cfm Rating, R-410A, 25 dBA, 29 dBA, 33 dBA, Steel, Galvanized, 35-7/16 in Overall Width, 9-13/16 in Overall Height, For Use With: Model AJ024BXJ3CH/AA, AJ036BXJ4CH/AA, AJ048BXJ5CH/AA, AJ020BXS3CH/AA, AJ024BXS4CH/AA, AJ030BXS4CH/AA, AJ036BXJ4CH/AA, AJ036BXS4CH/AA, AJ048BXJ5CH/AA Samsung Outdoor Units, Additional Information: 27-9/16 in D Dimensions
Additional Information27-9/16 in D Dimensions
Amperage Rating2.1 A
BTU Rating15000 Btu/hr
CFM Rating307 cfm, 374 cfm, 441 cfm
FinishGalvanized
Frequency Rating60 Hz
MaterialSteel
Number of Fan Speeds3
Overall Height9-13/16 in
Overall Width35-7/16 in
Phase1 ph
Power Rating153 W
Refrigerant TypeR-410A
SeriesFJM Series
Sound Level25 dBA, 29 dBA, 33 dBA
Suitable For Use WithModel AJ024BXJ3CH/AA, AJ036BXJ4CH/AA, AJ048BXJ5CH/AA, AJ020BXS more...Model AJ024BXJ3CH/AA, AJ036BXJ4CH/AA, AJ048BXJ5CH/AA, AJ020BXS3CH/AA, AJ024BXS4CH/AA, AJ030BXS4CH/AA, AJ036BXJ4CH/AA, AJ036BXS4CH/AA, AJ048BXJ5CH/AA Samsung Outdoor Units less
Voltage Rating208/230 V
High voltage terminal block temperature sensor to disable unit in the event overheating of power connection
Built-in condensate pump with maximum 29 in lift from the bottom of the unit, check valve and float switch that disables indoor unit during overflow detection
System energy consumption can be viewed using Samsung SmartThings mobile app (not revenue-grade, for reference only)
The indoor unit shall be powered by the outdoor unit
The unit shall be constructed of insulated, galvanized steel
The heat exchanger shall be mechanically bonded fin to copper tube
Indoor fan is a twin, backward curved centrifugal type with a single fan motor
Three-fan speed settings and auto setting
Control signal shall be a DDC-type signal
Interconnect control wire between outdoor and indoor unit shall be two 16 AWG
Dual set temperature support when connected to MWR-WG00UN advanced wired controller
The system shall integrate with the Samsung Controls Solution
Field provided filtration is recommended
Pressure drop across the filter must be factored into the total ESP