Samsung Max Heat® Heat Pump Condensing Unit, Series: FJM Series, 208/230 V, 12.2/13 A, 60 Hz, 1 ph Phase, 36600 Btu/hr Heating, 34000 Btu/hr Cooling, 3320 cfm Heating CFM Rating, 12.5 EER Rating, 21.5 SEER, 9.5 HSPF, Inverter Twin BLDC Rotary Compressor, R-410A Refrigerant, 1/4 in Liquid Line, 3/8 in, 1/2 in Suction Line, 55 dBA Heating Sound Level, 52 dBA Cooling Sound Level, Steel, Finish: Galvanized/Powder-Coated, -13 to 75 deg F Heating Operating Temperature, 14 to 114.8 deg F Cooling Operating Temperature, 13 in Overall Length, 37 in Overall Width, 47-5/8 in Overall Height, Additional Information: 4-Port
Additional Information
4-Port
Amperage Rating
12.2/13 A
Compressor Type
Inverter Twin BLDC Rotary
Cooling BTU Rating
34000 Btu/hr
Cooling Operating Temperature
14 to 114.8 deg F
Cooling Sound Level
52 dBA
EER Rating
12.5
Finish
Galvanized/Powder-Coated
Frequency Rating
60 Hz
HSPF Rating
9.5
Heating BTU Rating
36600 Btu/hr
Heating CFM Rating
3320 cfm
Heating Operating Temperature
-13 to 75 deg F
Heating Sound Level
55 dBA
Liquid Line Size
1/4 in
Material
Steel
Overall Height
47-5/8 in
Overall Length
13 in
Overall Width
37 in
Phase
1 ph
Refrigerant Type
R-410A
SEER Rating
21.5
Series
FJM Series
Suction Line Size
3/8 in, 1/2 in
Voltage Rating
208/230 V
- The Samsung Max Heat® system shall provide high heating capacity at -13 deg F (-25 deg C) outside temperature
- The outdoor unit shall supply power individually to the indoor units via 14 AWG X 3 power wire
- The outdoor unit shall have a base pan heater as standard to ensure optimal defrost cycle water drainage
- Auto-restart after power loss
- Available maximum current setting option to reduce operating current
- System energy consumption can be viewed using Samsung SmartThings mobile app (not revenue grade, for reference only)
- Soft-start to reduce current demand during compressor start
- Auto or manual addressing of indoor units
- The outdoor unit shall be galvanized steel with a baked on powder coated finish for durability
- The heat exchanger shall be mechanically bonded fin to copper tube
- Control signal shall be a DDC type signal
- Interconnect control wire between outdoor and indoor units shall be 16AWG X 2
- Controls shall integrate with a BMS system
- The system shall integrate with the Samsung Controls solution
- The refrigerant shall be R410A
- The compressor shall be hermetically sealed, inverter controlled, Twin BLDC Rotary
- Refrigerant flow shall be controlled by 4 separate electronic expansion valves at outdoor unit
-
Instruction/Installation Manual
https://assets.unilogcorp.com/267/ITEM/DOC/Samsung_AJ030CXS4CH_AA_Instruction_Installation_Manual.pdf
-
Service Manual
https://assets.unilogcorp.com/267/ITEM/DOC/Samsung_AJ020BXJ2CH_Service_Manual.pdf
-
Submittal