Samsung Standard Condensing Outdoor Unit, FJM Series, 208 to 230 V, 17.4 A Cooling, 16.4 A Heating, 125 W, 60 Hz, 1 ph, 48000 Btu/hr Heating, 46000 Btu/hr Cooling, 3320 cfm Heating CFM Rating, 3320 cfm Cooling CFM Rating, 11.7 EER Rating, 20 Ducted, 20.5 Mixed, 21 Non-Ducted SEER, 8.6 Ducted, 8.8 Mixed, 9 Non-Ducted HSPF, BLDC Inverter Driven Twin Rotary Compressor, R-32 Refrigerant, 1/4 in Liquid Line, 1/2 in, 3/8 in Suction Line, 40 A Fuse Rating, Inverter Drive, Tonnage: 3.83 ton, 55 dBA Heating Sound Level, 52 dBA Cooling Sound Level, Steel, Galvanized/Powder-Coated, 5 to 75 deg F Heating Operating Temperature, 14 to 115 deg F Cooling Operating Temperature, 13 in Overall Length, 37 in Overall Width, 47-5/8 in Overall Height
Amperage Rating17.4 A Cooling, 16.4 A Heating
Compressor TypeBLDC Inverter Driven Twin Rotary
Cooling BTU Rating46000 Btu/hr
Cooling CFM Rating3320 cfm
Cooling Operating Temperature14 to 115 deg F
Cooling Sound Level52 dBA
Correct Item GroupMulti Zone Outdoor Units
Drive TypeInverter
EER Rating11.7
FinishGalvanized/Powder-Coated
Frequency Rating60 Hz
Fuse Rating40 A
HSPF Rating8.6 Ducted, 8.8 Mixed, 9 Non-Ducted
Heating BTU Rating48000 Btu/hr
Heating CFM Rating3320 cfm
Heating Operating Temperature5 to 75 deg F
Heating Sound Level55 dBA
Liquid Line Size1/4 in
MaterialSteel
Overall Height47-5/8 in
Overall Length13 in
Overall Width37 in
Phase1 ph
Power Rating125 W
Refrigerant TypeR-32
SEER Rating20 Ducted, 20.5 Mixed, 21 Non-Ducted
SeriesFJM Series
Suction Line Size1/2 in, 3/8 in
Tonnage3.83 ton
Voltage Rating208 to 230 V
Auto-restart after power loss
Available maximum current setting option to reduce operating current
System energy consumption can be viewed using the Samsung SmartThings mobile app (not revenue grade, for reference only)
Soft-start to reduce current demand during compressor start
The outdoor unit shall supply power individually to the indoor units via 14 AWG X 3 power wire
The outdoor unit shall be galvanized steel with a baked-on powder coated finish for durability
The heat exchanger shall be mechanically bonded fin to copper tube
The system shall utilize low-GWP R-32 refrigerant
Refrigerant flow shall be controlled by an electronic expansion valve at the outdoor unit
The system shall include an R32 alarm output plug on indoor units with refrigerant leak detectors and outdoor unit for notification of R32 leak detection when refrigerant leak detectors are installed and configured (MIM-B14U accessories are required)
Control signal shall be a DDC type signal
Interconnect control wire between outdoor and indoor units shall be 16AWG X 2
The system shall integrate with the Samsung Central Controls solution