Outdoor unit for CAC slim duct, duct S, WindFree™ four way cassette, WindFree™ mini four way cassette, WindFree™ one way cassette, 360 cassette, multi-position air handler, console and high wall units.
Samsung Duct Split System Outdoor Unit, 208-230 V, 32.2 A, 60 Hz, 1 ph Phase, 2 Fan Speeds, 11000 to 63000 Btu/hr Heating, 12000 to 46000 Btu/hr Cooling, 1236 cfm Heating CFM Rating, 1236 cfm Cooling CFM Rating, 9.2 EER Rating, 17.5, 18.1 SEER, 8.8, 8.4 HSPF, 3/8 in Liquid Line, 5/8 in Suction Line, 55 dBA Heating Sound Level, 53 dBA Cooling Sound Level, Steel, Finish: Galvanized, -4 to 75 deg F Heating Operating Temperature, 23 to 122 deg F Cooling Operating Temperature, 37 in Overall Width, 47-11/16 in Overall Height, Additional Information: Single-Zone, 13 in D Dimensions
Additional InformationSingle-Zone, 13 in D Dimensions
Amperage Rating32.2 A
Cooling BTU Rating12000 to 46000 Btu/hr
Cooling CFM Rating1236 cfm
Cooling Operating Temperature23 to 122 deg F
Cooling Sound Level53 dBA
EER Rating9.2
FinishGalvanized
Frequency Rating60 Hz
HSPF Rating8.8, 8.4
Heating BTU Rating11000 to 63000 Btu/hr
Heating CFM Rating1236 cfm
Heating Operating Temperature-4 to 75 deg F
Heating Sound Level55 dBA
Liquid Line Size3/8 in
MaterialSteel
Number of Fan Speeds2
Overall Height47-11/16 in
Overall Width37 in
Phase1 ph
SEER Rating17.5, 18.1
Suction Line Size5/8 in
Voltage Rating208-230 V
The outdoor unit shall supply power to indoor unit via 14 AWG x 3 power wire
High voltage terminal block temperature sensor to disable unit in the event of power connection overheating
Integral condensate pump with maximum 29 in lift from bottom of the unit with check valve and float switch that disables indoor should condensate overflow be detected
Auto restart after power loss
Soft-start compressor minimizing current inrush
All heat exchangers shall be mechanically bonded aluminum fin to copper tube
The compressor shall be hermetically sealed, inverter-controlled BLDC rotary-type
Refrigerant flow shall be controlled by an electronic expansion valve at outdoor unit
Air filtration shall be field provided
Pressure drop across field-supplied filter must be factored into the total ESP